• 検索結果がありません。

(1) I/O assignment example

System configuration example (same as in 3.1.1)

When utilizing existing A (Large Type) and AnS (Small Type) modules with the Q Series CPU, set the existing module's I/O addresses to the existing addresses with the PC parameter I/O assignment settings. Assign the

● Parameter setting example

Model Type

4 N/A Empty

Point Address

16 170

1 2 3 0

Intelli Intelli Empty

Intelli QJ71BR11

QJ71E71-100 N/A

QJ61BT11N

32 32 16 32

120 140 160 100

5

Model Type

6

10 11 12 9 8 7

Input Empty

Intelli Empty Empty Intelli Intelli Output AX41

Main base unit (Q38B)

Extesion base unit (QA68B)

N/A

A68DAI-S1 N/A N/A A68AD A68AD AY10

Point Address

32 32

32 32 32 32 32 16

00 20

90 B0 D0 70 50 40

Tip

• Assign the I/O numbers in the following order: Q Series to A Series or A Series to Q Series.

• When the order is mixed (i.e., Q Series -> A Series -> Q Series), the CPU does not start up due to an error.

•‥The‥I/O‥addresses‥do‥not‥need‥to‥be‥changed‥when‥reutilizing‥existing‥A‥(Large‥Type)‥and‥AnS‥

(Small‥Type)‥modules‥with‥Q‥Series‥CPU‥and‥mounting‥the‥modules‥on‥QA6฀B/A6฀B+QA6ADP‥

or‥QA1S6฀B.‥This‥can‥greatly‥reduce‥program‥modification‥time.

•‥The‥A‥(Large‥Type)‥and‥AnS‥(Small‥Type)‥modules‥can‥be‥used‥with‥the‥same‥I/O‥addresses,‥so‥

there‥is‥no‥need‥to‥change‥the‥external‥wiring‥numbers.‥

Utilize‥existing‥A‥(Large‥Type)‥and‥AnS‥(Small‥Type)‥modules‥without‥changing‥I/O‥

addresses

● System configuration example of I/O assignment (1) I/O assignment example

When utilizing existing AnS (Small Type) modules with the L Series CPU, set the existing module's I/O addresses to the existing addresses with the PC parameter I/O assignment settings. Assign the addresses for the modules mounted onto the main base unit after the existing module. This will greatly reduce the program modification time.

• Assign the I/O numbers in the following order: L Series to A Series or A Series to L Series.

• When the order is mixed (i.e., L Series •

*

*1: Set the final address of the AnS Series modules on the extension base unit + 1 or higher.

*2: Setting when LA1S extension base is connected.

*3: "n" is the final slot number on the main base block side.

*4: The existing program can be used without changing I/O addresses by setting the existing AnS Series module addresses.

n+3 n+4 n+5 n+2 n+1

50

3.4.2 When replacing with L Series

The following is an example of how to reuse the program without modifying the I/O addresses when replacing the CPU with an L Series CPU and keeping the existing I/O modules on a LA1S extension base unit.

A1S61P

A35B

A2SHCPU A1SX41 A1SY41P A1SY10 A1SD61 A1SJ71C24-R2 L61P L02CPU Branch module

Main base block

LA1S65B

LJ71C24 End cover

LC06E

Current configuration After replacement

Replace with an L Series module, and set on the main base block Set on the LA1S extension base unit

Module replaced from AnS Series

Replace the module which cannot be mounted with an L Series module.

Existing AnS Series modules

A1S61P A1SY41P A1SY10 A1SD61

A1SX41 Empty

•‥The‥I/O‥addresses‥do‥not‥need‥to‥be‥changed‥when‥reutilizing‥existing‥AnS‥(Small‥Type)‥module‥

with‥L‥Series‥CPU‥and‥mounting‥the‥module‥on‥LA1S6□B‥or‥LA1S51B.‥This‥can‥greatly‥reduce‥

the‥program‥modification‥time.

•‥The‥AnS‥(Small‥Type)‥module‥can‥be‥used‥with‥the‥existing‥I/O‥addresses,‥so‥there‥is‥no‥need‥to‥

change‥the‥external‥wiring‥numbers.

Solution and Benefit

3.4 Utilize existing A (Large Type) and AnS (Small Type) modules without changing I/O addresses

Parameter setting example

Tip

• Assign the I/O numbers in the following order: L Series to A Series or A Series to L Series.

• When the order is mixed (i.e., L Series -> A Series -> L Series), the CPU does not start up due to an error.

• "GX Works2" is required to set the I/O assignment of LA1S extension base unit.

(LCPU main base block side)

Model

Slot Type

4

Points Start XY *1

1 2 3 0*2 CPU

Intelli

(Set when adding new modules) Main base

block

LJ71C24 N/A L6EXB

32 16

110 Built-in I/O function 100

Branch (for LA1S extension)

(Set to "130" or higher according to the number of points occupied by the modules)

*1: Set the final address of the AnS Series modules on the extension base unit + 1 or higher.

In this setting example, the start XY of the main base block unit is set to "XY100".

*2: Setting when LA1S extension base is connected.

When an extension base block is connected, set "Branch."

*3: "n" is the final slot number on the main base block side.

*4: The existing program can be used without changing I/O addresses by setting the existing AnS Series module addresses.

Slot *3

n+3 n+4 n+5 n+2 n+1

Output Output

Empty Intelli Input Extension

base unit

N/A A1SY10 A1SX41 A1SY41P

A1SD61

16 32

32 Optional

32 40 50 70 00 20

(LA1S extension base side)

Model

Type Points Start XY *4

A35B

LA1S65B

•‥The‥I/O‥addresses‥do‥not‥need‥to‥be‥changed‥when‥reutilizing‥existing‥AnS‥(Small‥Type)‥module‥

with‥L‥Series‥CPU‥and‥mounting‥the‥module‥on‥LA1S6□B‥or‥LA1S51B.‥This‥can‥greatly‥reduce‥

the‥program‥modification‥time.

•‥The‥AnS‥(Small‥Type)‥module‥can‥be‥used‥with‥the‥existing‥I/O‥addresses,‥so‥there‥is‥no‥need‥to‥

change‥the‥external‥wiring‥numbers.

The following is an example of replacing a MELSECNET(ΙΙ) coaxial loop system's master station with a Q Series system and upgrading the network to a MELSECNET/10 coaxial bus system.

● Instructions

(1) Replace one of the MELSECNET(ΙΙ) stations with the Q Series.

(2) Replace the complete MELSECNET(ΙΙ) system with MELSECNET/10 coaxial bus system.

(3) Replace the CPU of each station with Q Series CPU sequentially, and eventually replace all CPUs with Q Series CPUs.

(4) Use the existing settings for the network parameters.

•‥ When‥an‥existing‥MELSECNET(ΙΙ)‥system‥consists‥of‥many‥stations,‥the‥complete‥network‥

system‥can‥be‥upgraded‥to‥MELSECNET/10‥while‥reusing‥existing‥cable‥installations.

•‥ By‥upgrading‥the‥entire‥network‥at‥once,‥the‥current‥network‥parameter‥settings‥can‥be‥used.

•‥ Once‥the‥network‥is‥updated,‥A‥Series‥stations‥can‥be‥replaced‥with‥the‥Q‥Series‥in‥any‥order‥

until‥all‥the‥stations‥are‥upgraded‥to‥the‥Q‥Series.

Solution and Benefit

R

R

A2NCPUR21 Q61P Q02U CPU I/O module I/O module

I/O module I/O module Empty

I/O module I/O module

I/O module I/O module

I/O module I/O module

I/O module I/O module I/O module I/O module

I/O module I/O module

I/O module I/O module

I/O module I/O module QJ71BR11

Master station

NET/ΙΙ (Coaxial loop)

NET/10 (Coaxial bus) Control station

ΙΙ

ΙΙ ΙΙ

ΙΙ

Current‥configuration Transitional‥step‥1 Transitional‥step‥2 Transition‥completed

Second replacement

Final

replacement Initial

replacement

(1) System configuration example

A2NCPUR21A2SHCPUA2NCPUR21A2NCPUR21 A2NCPUR21A2SHCPUA2NCPUR21A2NCPUR21

EmptyA1SJ71AR21EmptyEmpty A1SJ71BR11 Q02U CPUQ01U CPUQ02U CPU Q02U CPUQ01U CPUQ02U CPUQ02U CPUQ02U CPU

Power supply modulePower supply modulePower supply modulePower supply modulePower supply module Power supply modulePower supply modulePower supply modulePower supply module

4.1.1 Replace MELSECNET(ΙΙ) coaxial loop with MELSECNET/10 coaxial bus system while retaining existing A Series CPUs