(1) I/O assignment example
● System configuration example (same as in 3.1.1)
When utilizing existing A (Large Type) and AnS (Small Type) modules with the Q Series CPU, set the existing module's I/O addresses to the existing addresses with the PC parameter I/O assignment settings. Assign the
●
● Parameter setting example
Model Type
4 N/A Empty
Point Address
16 170
1 2 3 0
Intelli Intelli Empty
Intelli QJ71BR11
QJ71E71-100 N/A
QJ61BT11N
32 32 16 32
120 140 160 100
5
Model Type
6
10 11 12 9 8 7
Input Empty
Intelli Empty Empty Intelli Intelli Output AX41
Main base unit (Q38B)
Extesion base unit (QA68B)
N/A
A68DAI-S1 N/A N/A A68AD A68AD AY10
Point Address
32 32
32 32 32 32 32 16
00 20
90 B0 D0 70 50 40
Tip
• Assign the I/O numbers in the following order: Q Series to A Series or A Series to Q Series.
• When the order is mixed (i.e., Q Series -> A Series -> Q Series), the CPU does not start up due to an error.
•‥The‥I/O‥addresses‥do‥not‥need‥to‥be‥changed‥when‥reutilizing‥existing‥A‥(Large‥Type)‥and‥AnS‥
(Small‥Type)‥modules‥with‥Q‥Series‥CPU‥and‥mounting‥the‥modules‥on‥QA6B/A6B+QA6ADP‥
or‥QA1S6B.‥This‥can‥greatly‥reduce‥program‥modification‥time.
•‥The‥A‥(Large‥Type)‥and‥AnS‥(Small‥Type)‥modules‥can‥be‥used‥with‥the‥same‥I/O‥addresses,‥so‥
there‥is‥no‥need‥to‥change‥the‥external‥wiring‥numbers.‥
Utilize‥existing‥A‥(Large‥Type)‥and‥AnS‥(Small‥Type)‥modules‥without‥changing‥I/O‥
addresses
● System configuration example of I/O assignment (1) I/O assignment example
When utilizing existing AnS (Small Type) modules with the L Series CPU, set the existing module's I/O addresses to the existing addresses with the PC parameter I/O assignment settings. Assign the addresses for the modules mounted onto the main base unit after the existing module. This will greatly reduce the program modification time.
●
• Assign the I/O numbers in the following order: L Series to A Series or A Series to L Series.
• When the order is mixed (i.e., L Series •
*
*1: Set the final address of the AnS Series modules on the extension base unit + 1 or higher.
*2: Setting when LA1S extension base is connected.
*3: "n" is the final slot number on the main base block side.
*4: The existing program can be used without changing I/O addresses by setting the existing AnS Series module addresses.
n+3 n+4 n+5 n+2 n+1
50
3.4.2 When replacing with L Series
The following is an example of how to reuse the program without modifying the I/O addresses when replacing the CPU with an L Series CPU and keeping the existing I/O modules on a LA1S extension base unit.
A1S61P
A35B
A2SHCPU A1SX41 A1SY41P A1SY10 A1SD61 A1SJ71C24-R2 L61P L02CPU Branch module
Main base block
LA1S65B
LJ71C24 End cover
LC06E
Current configuration After replacement
Replace with an L Series module, and set on the main base block Set on the LA1S extension base unit
Module replaced from AnS Series
Replace the module which cannot be mounted with an L Series module.
Existing AnS Series modules
A1S61P A1SY41P A1SY10 A1SD61
A1SX41 Empty
•‥The‥I/O‥addresses‥do‥not‥need‥to‥be‥changed‥when‥reutilizing‥existing‥AnS‥(Small‥Type)‥module‥
with‥L‥Series‥CPU‥and‥mounting‥the‥module‥on‥LA1S6□B‥or‥LA1S51B.‥This‥can‥greatly‥reduce‥
the‥program‥modification‥time.
•‥The‥AnS‥(Small‥Type)‥module‥can‥be‥used‥with‥the‥existing‥I/O‥addresses,‥so‥there‥is‥no‥need‥to‥
change‥the‥external‥wiring‥numbers.
Solution and Benefit
3.4 Utilize existing A (Large Type) and AnS (Small Type) modules without changing I/O addresses
●
● Parameter setting example
Tip
• Assign the I/O numbers in the following order: L Series to A Series or A Series to L Series.
• When the order is mixed (i.e., L Series -> A Series -> L Series), the CPU does not start up due to an error.
• "GX Works2" is required to set the I/O assignment of LA1S extension base unit.
(LCPU main base block side)
Model
Slot Type
4
Points Start XY *1
1 2 3 0*2 CPU
Intelli
(Set when adding new modules) Main base
block
LJ71C24 N/A L6EXB
32 16
110 Built-in I/O function 100
Branch (for LA1S extension)
(Set to "130" or higher according to the number of points occupied by the modules)
*1: Set the final address of the AnS Series modules on the extension base unit + 1 or higher.
In this setting example, the start XY of the main base block unit is set to "XY100".
*2: Setting when LA1S extension base is connected.
When an extension base block is connected, set "Branch."
*3: "n" is the final slot number on the main base block side.
*4: The existing program can be used without changing I/O addresses by setting the existing AnS Series module addresses.
Slot *3
n+3 n+4 n+5 n+2 n+1
Output Output
Empty Intelli Input Extension
base unit
N/A A1SY10 A1SX41 A1SY41P
A1SD61
16 32
32 Optional
32 40 50 70 00 20
(LA1S extension base side)
Model
Type Points Start XY *4
A35B
LA1S65B
•‥The‥I/O‥addresses‥do‥not‥need‥to‥be‥changed‥when‥reutilizing‥existing‥AnS‥(Small‥Type)‥module‥
with‥L‥Series‥CPU‥and‥mounting‥the‥module‥on‥LA1S6□B‥or‥LA1S51B.‥This‥can‥greatly‥reduce‥
the‥program‥modification‥time.
•‥The‥AnS‥(Small‥Type)‥module‥can‥be‥used‥with‥the‥existing‥I/O‥addresses,‥so‥there‥is‥no‥need‥to‥
change‥the‥external‥wiring‥numbers.
The following is an example of replacing a MELSECNET(ΙΙ) coaxial loop system's master station with a Q Series system and upgrading the network to a MELSECNET/10 coaxial bus system.
● Instructions
(1) Replace one of the MELSECNET(ΙΙ) stations with the Q Series.
(2) Replace the complete MELSECNET(ΙΙ) system with MELSECNET/10 coaxial bus system.
(3) Replace the CPU of each station with Q Series CPU sequentially, and eventually replace all CPUs with Q Series CPUs.
(4) Use the existing settings for the network parameters.
•‥ When‥an‥existing‥MELSECNET(ΙΙ)‥system‥consists‥of‥many‥stations,‥the‥complete‥network‥
system‥can‥be‥upgraded‥to‥MELSECNET/10‥while‥reusing‥existing‥cable‥installations.
•‥ By‥upgrading‥the‥entire‥network‥at‥once,‥the‥current‥network‥parameter‥settings‥can‥be‥used.
•‥ Once‥the‥network‥is‥updated,‥A‥Series‥stations‥can‥be‥replaced‥with‥the‥Q‥Series‥in‥any‥order‥
until‥all‥the‥stations‥are‥upgraded‥to‥the‥Q‥Series.
Solution and Benefit
R
R
A2NCPUR21 Q61P Q02U CPU I/O module I/O module
I/O module I/O module Empty
I/O module I/O module
I/O module I/O module
I/O module I/O module
I/O module I/O module I/O module I/O module
I/O module I/O module
I/O module I/O module
I/O module I/O module QJ71BR11
Master station
NET/ΙΙ (Coaxial loop)
NET/10 (Coaxial bus) Control station
ΙΙ
ΙΙ ΙΙ
ΙΙ
Current‥configuration Transitional‥step‥1 Transitional‥step‥2 Transition‥completed
Second replacement
Final
replacement Initial
replacement
(1) System configuration example
A2NCPUR21A2SHCPUA2NCPUR21A2NCPUR21 A2NCPUR21A2SHCPUA2NCPUR21A2NCPUR21
EmptyA1SJ71AR21EmptyEmpty A1SJ71BR11 Q02U CPUQ01U CPUQ02U CPU Q02U CPUQ01U CPUQ02U CPUQ02U CPUQ02U CPU
Power supply modulePower supply modulePower supply modulePower supply modulePower supply module Power supply modulePower supply modulePower supply modulePower supply module
4.1.1 Replace MELSECNET(ΙΙ) coaxial loop with MELSECNET/10 coaxial bus system while retaining existing A Series CPUs