(3) Parameter of standby station *1

: Compatible, : Partial change required, ×: Incompatible

*1 Standby station is a station type of simple dual-structured system.

Only the following CPU modules support the simple dual-structured system.

• High Performance model QCPU

• Process CPU Parameter

name

Description

Compat-ibility Precautions for replacement QnA/QnAS series

MELSECNET/10 module

Q series MELSECNET/H module (MELSECNET/10 mode)

Network parameter

Network type Network type

Starting I/O No. Starting I/O No.

Network No. Network No.

- Group No. Set the group No. in GX Developer

network parameters.

- Mode Set the mode in GX Developer

network parameters.

Standby station compatible module

Standby station compatible module

Routing parameters Routing parameters Valid module during other

station access

Valid module during other station access

REPLACEMENT OF THE MELSECNET/10 (PLC TO PLC NETWORK)

4

4.6.1 Comparison of link special relay (SB)/link special register (SW)

The table below shows only link special relay (SB) and link special register (SW) to be used in interlock program.

Device name and device No. of MELSECNET/H module are described in link device of internal MELSECNET/H module.

Changing sequence program should be performed after checking the refreshed device of link device in refresh parameters.

(1) AnN/AnA/AnSCPU (excluding AnUS(H)CPU)

When MELSECNET/10 module is mounted to the CPU module of the AnN/AnA/AnSCPU (excluding AnUS(H)CPU), link special relay (SB) and link special register (SW) are assigned to special relay and special register of CPU module.

For replacing with a MELSECNET/H module, change sequence program in reference to the following.

(a) Link special relay (SB)

: Compatible, : Partial change required, ×: Incompatible

(To next page)

4.6 Program Comparisons

AnN/AnA/AnSCPU MELSECNET/10 module

QCPU

MELSECNET/H module

Compat-ibility Precautions for replacement

Number Name Description Number Name Description

M9204 LRDP instruction complete

OFF : Not completed

ON : Completed - -

-LRDP instruction cannot be used.

When using it in sequence program, delete corresponding part.

M9205 LWTP instruction complete

OFF : Not completed

ON : Completed - -

-LWTP instruction cannot be used.

When using it in sequence program, delete corresponding part.

M9211 Module status OFF : Normal

ON : Abnormal SB0020 Module status OFF : Normal ON : Abnormal

M9240 Online host status

OFF : Online ON : Offline,

self-loopback test, station-to-station test

SB0043 Online switch (host station)

OFF : Online ON : Other than

online

M9241 Forward loop status

OFF : Normal

ON : Abnormal SB0090 Host loop status OFF : Normal ON : Abnormal

When SB0090 turns on, check the loop condition with SW0090, or check by host bit of SW0091 to SW0094.

M9242 Reverse loop status

OFF : Normal

ON : Abnormal SB0090 Host loop status OFF : Normal ON : Abnormal

When SB0090 turns on, check the loop condition with SW0090, or check by host bit of SW0095 to SW0098.

M9243 Loopback status

OFF : Loopback inexecution ON : Loopback

execution

SB0090 Host loop status OFF : Normal ON : Abnormal

When SB0090 turns on, check the loop condition with SW0090, or check by SW0099 or SW009A.

M9246

Data not received (Control station)

OFF : Received

ON : Not received - -

-When using it in sequence program, delete corresponding part.

M9250 Parameter unreceived

OFF : Received

ON : Not received SB0054 Parameter receive status

OFF : Receive completed ON : Unreceived M9251 Communication

status

OFF : Normal

ON : Abnormal SB0049 Host data link status

OFF : Normal ON : Abnormal

REPLACEMENT OF THE MELSECNET/10 (PLC TO PLC NETWORK)

4

: Compatible, : Partial change required, ×: Incompatible

(b) Link special register (SW)

: Compatible, : Partial change required, ×: Incompatible AnN/AnA/AnSCPU

MELSECNET/10 module

QCPU

MELSECNET/H module

Compat-ibility Precautions for replacement

Number Name Description Number Name Description

M9252 Loop test status

OFF : Not being executed ON : Forward loop

test/reverse loop test execution underway

SB00AE

Offline testing response designation

OFF : No response ON : Response

M9253 Control station operation status

OFF : RUN or STEP RUN ON : STOP or

PAUSE

SW0084 to SW0087

Each station CPU RUN status

Stores the CPU RUN status of each station.

(Including the host)

M9254 Other station operation status

OFF : All stations are in the RUN or STEP RUN status ON : Any station in

the STOP or PAUSE status exist

SB0084

Each station CPU RUN status

OFF : All stations are in the RUN or STEP RUN status ON : Station in the

STOP or PAUSE status exist (including the host)

M9255

Other station communication status

OFF : All stations normal ON : Any error

station identified

SB0074 Cyclic transmission status of each station

OFF : All stations are executing data linking ON : Stations that

are not executing data linking exist

AnN/AnA/AnSCPU MELSECNET/10 module

QCPU

MELSECNET/H module

Compat-ibility Precautions for replacement

Number Name Description Number Name Description

D9243 Host station number

Stores the station

number of the host. SW0042 Station No. Stores the station number of the host.

D9244 Maximum station No.

Stores the maximum station No. set in network parameters.

SW0059 Total number of link stations

Stores the total number of link stations set in network parameters.

D9245 Communication error count

Accumulates and stores the communication error times.

SW00B8 to SW00C7

Error counters

Accumulates and stores the various error time.

The error count for each error cause is stored.

D9248 to D9251

Other station CPU RUN status

Stores the CPU RUN status of other station.

SW0084 to SW0087

Each station CPU RUN status

Stores the RUN status of each station.

(Including the host) D9252

to D9255

Data link status of other station

Stores the data link status of other station.

SW0074 to SW0077

Cyclic transmission status of each station

Stores the cyclic transmission status of each station.

REPLACEMENT OF THE MELSECNET/10 (PLC TO PLC NETWORK)

4

(2) AnU/AnUS(H)/QnA/QnASCPU

The following device name and device No. are described in link device of internal MELSECNET/10 or MELSECNET/H module.

Changing sequence program should be performed after checking the refreshed device of link device in refresh parameters.

(a) Link special relay (SB)

: Compatible, : Partial change required, ×: Incompatible

(b) Link special register (SW)

: Compatible, : Partial change required, ×: Incompatible

Remarks

For link special relay (SB) and link special register (SW) that are not described in this section, refer to each manual.

Item

Number

Compat-ibility

Precautions for replacement AnU/AnUS(H)/QnA/

QnASCPU MELSECNET/10 module

QCPU MELSECNET/H module

Module status SB0020 SB0020

Baton pass status (host) SB0047 SB0047

Data link status of each

station SB0049 SB0049

Baton pass status of each

station SB0070 SB0070

Cyclic transmission status of

each station SB0074 SB0074

Item

Number

Compat-ibility

Precautions for replacement AnU/AnUS(H)/QnA/

QnASCPU MELSECNET/10 module

QCPU MELSECNET/H module Baton pass status of each

station SW0070 to SW0073 SW0070 to SW0073

Cyclic transmission status of

each station SW0074 to SW0077 SW0074 to SW0077

REPLACEMENT OF THE MELSECNET/10 (PLC TO PLC NETWORK)

4

4.6.2 Comparison of dedicated instructions (1) A/AnSCPU

: Compatible, : Partial change required, ×: Incompatible